*************** v2.12 ********** Corrected logic where ZXM appears in device list, but device count is not incremented. *************** v2.11 ********** Re-Alignment of Carel Faults *************** v2.10 *************** Added logic in U2 for the parsing of hardware ID from Power+ via CIM for smart skip speed selection. Support of new Carel inverter *************** v2.03 *************** 1. Software compatibility: v2.03 for PCB, v1.0 to v1.1B (all releases to date) a. Interoperability i. AWC99B01R ii. MIM, v1.00 to v1.01 (all releases to date) iii. WXM, v1.00 to v1.01 (all releases to date) iv. ZXM, v1.00 2. Zoning Releases: a. Firmware v2.03 corrects: i. Loop pump failed to speed up on transition from standby to active demand in all modes using loop pump (Heat, Cool & DHW) when loop flow <2.0gpm ii. Compressor start condition corrected to match specification – now starts when loop flow >= 2.0gpm, instead of >2.0gpm iii. Corrects failure to start compressor if loop speed rises to 90% before loop flow >=2.0gpm if loop option = Parallel per 4.18.9